English | Japanese | German | Russian
Chinese-Traditional | Chinese-Simplified
Home Profile Product Sale Support Driver FAQ Sitemap E-mail

Multifunction Power Meter
SPM-1600

Product Catalog
(Please press icon for complete product catalog)

SPM-1600
- Class 0.5 revenue accuracy (with DC immunity option)
- Wide range of current measurement (from 0.001 Ib to 6.67 Ib)
- Bi-directional energy measurement
- Multi-tariff with TOU (up to 4 tariffs)
- Full power parameters measurement
- Power quality monitoring and analysis (with THD, sag/swell option)
- Four quadrant measurement
- 96~528 VAC input with any phase power supply
- Energy calculation under phase lost
- Wide range of operation temperature -30°C~70°C
- Configurable block or rolling demand
- Configurable crystal or power line time-base
- IEC 62053-22, ANSI C12.20 accuracy - 10 years certified life
Specifications
Power
96~528 VAC, 50/60 Hz, 3 phase power supply
Accuracy
Class 0.5 (IEC 62053-22 or ANSI C12.20)
Range
Voltage 96~528 Vac
Current
Model SPM-1605: Ib 5A, 2.5mA~20 A
Model SPM-1630: Ib 30A, 30mA~150A
Starting Current
2.5 mA for SPM-1605, 30 mA for SPM-1630
Temperature range
-30°C~70°C inside meter cover
Humidity range
0 to 100% noncondensing
Primary time base
Power line frequency (50/60 Hz), software configurable to crystal
Secondary time base
< 0.01%
Meter base
Form 16A (14A, 15A, 17A) for SPM-1630
Form 10A (9A) for SPM-1605
Battery
LiSOCl2, 950 mAhr
Communication port
ANSI Type II optical port
Communication option board
RS-232, RS-485, Modem, LonTalks PLC, GPRS
Application standard
ANSI C12.1 / C12.10 / C12.18 / C12.19 / C12.20 / C12.21
TOU
4 tariff with season, day type, and time zone settings
Load profile memory
512KByte configurable up to 20 channels (With the LP option)
Power quality measure
Voltage and current THD per phase, programmable sag/swell recording (With the LP option)
Harmonics analysis
Event driven log, plotted by MeterGen(With LP option)
Programming software
MeterGen for meter configuration
MeterComm for DAP communication
LoadProfiler for load curve report
3 level security protection.
Communication protocol
ANSI C12.18, ANSI C12.19(with Modem option)
ModBus (with RS-232/485 option)
Surge voltage withstand
ANSI C37.90.1, ANSI C62.4.1, IEC 61000-4-4
Calibration
Automatic software calibration
Dimension
188mm(W) x 235mm(H) x 156mm(D)
Net weight
2.1 Kg
Ordering Information
Multifuncion Power Meter SPM-1600
Accessory
SPM1600 - SW01 MeterGen programming and Windows communication software
SPM1600 - SW02 MeterComm DAP communication software
SPM1600 - SW03 LoadProfiler software
SPM1600 - CM01 Telephone Modem communication board
SPM1600 - CM02 LonTalks PLC communication board
SPM1600 - CM03 RS-232 communication board
SPM1600 - CM04 RS-485 communication board
SPM1600 - CM05 GPRS communication board